AC Power Distribution

AC PDUs

Recommended for new builds

Spectrum Control Inc. is introducing a new best-in-class AC Power Distribution Unit (PDU) product line designed specifically for highly reliable operation in harsh environments. High performance, a full feature set, and a ruggedized design combined with a focus on manufacturability and component availability deliver excellent value to our customers.

The platform approach facilitates minor hardware customizations such as input and output connectors and cables, and flexible configuration and operation via software interface.

 

Get More Info

Why Good Power Management Matters


Modern battlefields are a high value mix of personnel, equipment and systems. Providing reliable power to support equipment and systems is an essential part of battlefield strategy.

Reliable power distribution and control means supporting both local decisions and remote control and management. And unlike other industrial or commercial PDUs, battlefield power systems must operate reliably in a wide range of hostile conditions, protecting the needs of the mission.

  • For Aerospace, Defense and Industrial customers that need to manage and protect high value assets in harsh environments.
     
  • Spectrum Control’s best in class AC & DC Power Distribution Units provide secure control and reliable protection unlike most COTS vendors who trade off reliability & ruggedness for cost.
  • We do this by building a ruggedized product with a full-featured modern controller supporting the latest security and interfaces combined with current, voltage and temperature monitoring on a per port basis.
     
  • Reliability and performance are demonstrated by our MIL-STD-810H and MIL-STD-461G qualification testing.

Features

General Operation

Secure remote access and control.

Front panel status display (OLED & LEDs).

Common control across AC/DC PDU’s and RF/ Microwave Systems.

  • Enables common UI (user interface) and single connection

Support logical interfaces including SSH, Telnet and Serial interfaces using proprietary ASCII based command line interface (CLI).

Supports SNMPv1/2c/3.

DHCP or Static IPv4 addressing over a Gigabit Ethernet physical layer.

Flexible configuration

Remote Monitoring and control of each outlet individually.

Configurable UP and DOWN Sequencing.

  • Configurable Channel Groups
  • Configurable soft breaker settings including configurable recover retries.

Configurable over and under alarm settings for voltage, current and temperature.

Auto Up Sequence, Group Enable or Individual Channel Enable following special events (power on, EPO).

4 Modes of control for each channel based on external sensor.

  • Turn ON if the temperature increases above a set threshold (cooling)
  • Turn ON if the temperature decreases below a set threshold (heating)
  • Turn ON if the temperature is within an upper and lower test point (Safe Operating Range), or
  • Turn ON if the temperature is outside an upper and lower test point (Alarm Mode)

Hardware

1 RU 19’’ rack mount package.

Designed for manufacturability, automated production test, emphasis on parts availability.

Front panel indicators for mains, channel, local / remote status.

OLED display for addressing, hour meter and additional status.

Ethernet (GigE) nickel-plated-shielded RJ45 and USB 2.0 type-C interfaces.

Input and output monitoring voltage / current / protection / EMI filtering.

Internal and external temperature sensors.

Hardware watchdog timer shuts down unit if control is non-responsive.

Ruggedized design, wide temperature range / low smoke wiring.

Conservatively rated for high MTBF and cool operation.

Operator Safeguards – Emergency Power Off (EPO) functionality.

Specifications

Input Characteristics

Input Voltage 85-132 / 170-250 VAC
Input Frequency 60 / 50 Hz +/- 3Hz
Line Current Capacity 30A
Input Voltage and Current Monitoring ○ Voltage measurement +/- 1%
○ Current measurement +/- 2.7%
Overload Protection 1P/20A or 1P/30A UL489
circuit breaker
Attached Power Cord 4ft NEMA 5-20P
Transient / Surge Protection UL 1449 MOVs, Line-to-Neutral, Line-to-Ground, Neutral-to-Ground

Thermal protection

Transient Energy (2mS): 100J

Peak Surge Current (8/20uS): 10kA single pulse

Maximum Clamping Voltage (8/20uS): 340V @ 100A pk
 (120V variant)

Maximum Clamping Voltage (8/20uS): 710V @ 100A pk
(240V variant)
EMI Filtering Power Line Filter (FHSA series) on input

30dB CM / 26dB DM @ 1MHz

55dB CM / 64dB DM @ 10MHz

45dB CM / 35dB DM @ 30MHz
No Output Load Power Consumption 30W

Output Characteristics

Output Voltage 85-132 / 170-250 VAC
Output Current 20A Maximum per Outlet, 30A Maximum Total Combined Load
Outlets (8) NEMA 5-20R
Output Voltage and Current Monitoring on each Outlet Voltage measurement +/- 1%

Current measurement +/- 2.7%

Mechanical Characteristics

Material Aluminum
Finish Powder Coat, Black,
Fine Texture
Lettering Silk Screen, White
Mounting Brackets accommodate
Front or Mid Mount
Weight 5kg

Communication

USB Type C connector
 10/100/1000 Base-T
(MIL-C-26482 RJ-45 Connector)

Operation Environment

Operating Temperature -40C to +50C
Storage Temperature -40C to +80C
Relative Humidity 0 – 95% (non-Condensing)
Elevation 0 – 3,050 meters
Sensor Internal and External Temperature Sensing

Environmental

MILSPEC MIL-STD-810H
○ 501.7 Procedure II
○ 507.6 Procedure II
○ 514.8 Procedure I
○ 516.8 Procedures IV & V
MIL-STD-461G